Place of use
Indoors and outdoors, in cable ducts, underground, in power and switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.
YVZ2V-U, YVZ2V-R, NYRY -Â Construction
Â
Conductor: | : rigid red copper wire, class  1 (Φ ≤ 4 mm²)  stranded circular compacted copper class 2 (Φ>4mm²) |
Insulation | : XLPE crosslinked polyethylene (no dry cool) / PVC |
Filler | : Filler |
Armoured | : Galvanized round steel wires. |
Inner covering | : Polyester tape |
Outer sheath | : PVC / PE |
YVZ2V-U, YVZ2V-R, NYRY -Â Technical data and tests | |
Standards | : NF C 32-321 C32-321/A1; IEC 60502-1 NF EN 60332-1-2; NF CÂ 15-100 |
Nominal voltage U0/U | : 0,6/1 kV |
Test voltage (50 Hz) | : 4 kV |
Maximun voltage Um | : 1,2 kV |
Maximun operating temperature | : +90° C |
Maximun short circuit temperature | : +250° C |
Min. operating temperature  (without mechanical shocks) |
: -25° C |
Minimum installation and use temp. | : -10° C |
Minimum bending radius per  D cable diameter (in mm) |
: 6 x D |
Maximum pulling stress | : 5 kg/mm² (of copper cross section) |
Core colours | single core : black two cores : blue-brown three  cores : brown-black-blue  (1,5/2,5 mmq); brown-black-gray (4 mmq)  or Y/G-blue-brown) four cores : blue-brown-black-gray (or Y/G instead blue) five cores : blue-brown-black-gray-Y/G (or black instead Y/G) |
Sheath colour | : black |
YVZ2V-U, YVZ2V-R, NYRY-Â Applications
This cable is for use on industrial sites and the upright columns of buildings. Particularly suited in cases of high operating temperatures and when high resistance to solar radiation and atmospheric agents is required.
Presents good resistance to low temperatures and chemical agents. It can be used without additional mechanical protection in open air, fixed to walls or in raceways, inside walkways, and in empty in constructions in general.
It can be laid underground with mechanical protection constucted from slabs, tiles, or bricks. It is not recommended to lay this cable in ground flooded for more than two months per year.
With appropriate mechanical protection it can be use in areas subject to risk of explosion, but in this case the permitted current load is reduced by 15%.
Â
Power cable 0.6/1 kVÂ -Â Other standards | |
German | :Â N2XY |
British | : CU/XLPE/PVC |
Serbian | : XP 00 |
Turkish | :Â YXV-U (-R) |
Romanian | : C2XY |
Â
DIMENSIONS | |||||||||
Cores number N° |
Cross section mm² |
Approx conductor diameter mm |
Insulation medium thickness mm |
Min. sheath thickness mm |
Max. external diameter mm |
Electric resistance at 20°C ohm/km |
Approx cable weight kg/km |
Current carrying air free A |
Current carrying burried A |
Single core | |||||||||
1x | 1.5 | 1.4 | 0.7 | 1.09 | 6.6 | 12.1 | 45 | 24 | 31 |
1x | 2.5 | 1.8 | 0.7 | 1.09 | 7 | 7.41 | 55 | 33 | 41 |
1x | 4 | 2.25 | 0.7 | 1.09 | 7.6 | 4.61 | 75 | 45 | 59 |
1x | 6 | 3.05 | 0.7 | 1.09 | 8.2 | 3.08 | 100 | 58 | 74 |
1x | 10 | 3.8 | 0.7 | 1.09 | 9.2 | 1.83 | 140 | 80 | 101 |
1x | 16 | 4.7 | 0.7 | 1.09 | 10.5 | 1.15 | 205 | 107 | 128 |
1x | 25 | 5.9 | 0.9 | 1.09 | 12.5 | 0.727 | 315 | 138 | 144 |
1x | 35 | 7.1 | 0.9 | 1.09 | 13.5 | 0.524 | 400 | 169 | 174 |
1x | 50 | 8 | 1 | 1.09 | 15 | 0.387 | 530 | 207 | 206 |
1x | 70 | 9.6 | 1.1 | 1.09 | 17 | 0.268 | 725 | 268 | 254 |
1x | 95 | 11.4 | 1.1 | 1.18 | 19 | 0.193 | 985 | 328 | 301 |
1x | 120 | 13.1 | 1.2 | 1.18 | 21 | 0.153 | 1260 | 382 | 343 |
1x | 150 | 14.6 | 1.4 | 1.26 | 23 | 0.124 | 1520 | 441 | 387 |
1x | 185 | 16.5 | 1.6 | 1.26 | 25.5 | 0.0991 | 1940 | 506 | 434 |
1x | 240 | 18.4 | 1.7 | 1.35 | 28.5 | 0.0754 | 2310 | 599 | 501 |
1x | 300 | 21.1 | 1.8 | 1.43 | 31 | 0.0601 | 3200 | 693 | 565 |
1x | 400 | 23.5 | 2 | 1.52 | 34.2 | 0.047 | 3931 | - | 639 |
1x | 500 | 26.5 | 2.2 | 1.6 | 38 | 0.0366 | 5020 | - | 713 |
1x | 630 | 30.1 | 2.4 | 1.69 | 44 | 0.0286 | 5324 | - | 785 |
Two cores | |||||||||
2x | 1.5 | 1.4 | 0.7 | 1.43 | 10.5 | 12.1 | 115 | 26 | 37 |
2x | 2.5 | 1.8 | 0.7 | 1.43 | 11.5 | 7.41 | 145 | 36 | 48 |
2x | 4 | 2.25 | 0.7 | 1.43 | 13 | 4.61 | 195 | 49 | 63 |
2x | 6 | 3.05 | 0.7 | 1.43 | 14 | 3.08 | 265 | 63 | 80 |
2x | 10 | 3.8 | 0.7 | 1.43 | 16 | 1.83 | 390 | 86 | 104 |
2x | 16 | 4.7 | 0.7 | 1.43 | 18.5 | 1.15 | 560 | 115 | 136 |
2x | 25 | 5.9 | 0.9 | 1.43 | 22 | 0.727 | 850 | 149 | 173 |
2x | 35 | 7.1 | 0.9 | 1.43 Our company is specialized in supplying high quality Capillary Tube.Capillary Copper Tube are critical parts used as restrictors against refrigerant flow and pressure in the refrigeration cycle of air conditions, electric refrigerators, showcases freezer, this copper tubing usually manufactured with fine precision, down to one thousandth of an inch. This precision allows airflow to be smoother, more uniform, and more closely monitored, making such applications as fluid & air restrictors much more useful. Capillary copper tubing has very small inside diameters.Production Standard: ASTM B280, ASTM B360 JISH3300 .etc.Our parts have been exported to over 50 countries all over the world. Capillary Tube Capillary Tube,Copper Capillary Tube,Air Conditioning Capillary Tube ZHEJIANG ICE LOONG ENVIRONMENTAL SCI-TECH CO.,LTD. , http://www.ice-loong.com |